Model 468 Voltage Transformer

FREQUENCY: 60 Hz.
STANDARD SECONDARY VOLTAGE: 120 Volts
INSULATION LEVEL: 600 Volt, 10 kV BIL full wave.
ACCURACY CLASS: +/- 0.6% at all burdens up to 7.5 VA and +1.5% 20 VA burden.
THERMAL RATING: 75 VA at 30oC. amb., 50 VA at 55oC. amb.

Terminals are brass studs No. 10-32 with one lockwasher, flatwasher and regular nut.

Approximate weight 4 lbs.