APPLICATION: Metering and relaying.
FREQUENCY: 50-400 Hz.
MAXIMUM SYSTEM VOLTAGE: 36.5kV, BIL 150kV full wave.
CONTINUOUS THERMAL CURRENT RATING FACTOR:
1.50 at 30oC amb., 1.33 at 55oC. amb.
2000:5 - 1.33 at 30oC amb., 1.00 at 55oC. amb.
2500:5 and 3000:5 - 1.00 at 30oC amb., 0.85 at 55oC. amb.
Primary terminals are plated copper bars, configured as specified.
Secondary terminals are brass screws No. 10-32 with one flatwasher and lockwasher.
Vacuum cast polyurethane resin. Dual bar spacing is 1/2 inch.
Approximate weight: 180 lbs.
*With a burden of BO.1 or greater connected to the secondary.
**Specify primary bus arrangement number (1 through 8).