Model PCL AC Current Transducer 0 - 75 Amps

Operating Range: Input 5 thru 75 Amps ac. Output: 4-20 mA dc.
Frequency: 50-60 Hz.

Ambient Temperature Range:
Effect on accuracy + 0.02%/ oC
Operating: -30 oC to +60 oC
Storage: -55 oC to +85 oC

Insulation Level:
600 Volts, 10 kV BIL full wave

Accuracy:
+ 0.5% F.S. maximum.
1% max. peak ripple on output.
Response Time: <150 ms (10 % to 90 %)
Output load (RL): 0-1000 .
Maximum output: 30 mA dc.
Supply Voltage Range: 120 Vac + 10 %.
Terminal are brass studs No. 10-32 with one flatwasher, lockwasher and regular nut.
Approximate weight: 1.0 lbs.

Available as PCL5, PCL20 and PCL75