APPLICATION: Metering and relaying.
FREQUENCY: 50-400 Hz.
MAXIMUM SYSTEM VOLTAGE: 36.5kV, BIL 150kV full wave.
CONTINUOUS THERMAL CURRENT RATING FACTOR: 1.50 at 30oC amb., 1.33 at 55oC. amb.
Primary terminals are 1/2-13 bolts with one Belleville washer.
Secondary terminals are brass screws No. 10-32 with one flatwasher and lockwasher.
Vacuum cast polyurethane resin.
Approximate weight:
T100 - 125 lbs.
T200 - 155 lbs.