APPLICATION: For energy management systems and instrumentation equipment.
FREQUENCY: 50-400 Hz.
INSULATION LEVEL: 0.6 kV, BIL 10 kV full wave.
CONSTRUCTION: The core and winding are encased in U.L. approved plastic.
CONTINUOUS THERMAL CURRENT RATING FACTOR: 1.33 at 30oC. amb., 1.0 at 55oC. amb.
Flexible leads are UL 1015, 105oC , #16 AWG, 36" long unless otherwise specified.
Approximate Weight 1.2 lbs.
Window Size 1.31"x 2.16"